Fabrication and Performance testing of Evaporative Air Cooler with Solar Liquid Desiccant Dehumidification

Authors

  • Ashish S. Utage Department of Mechanical Engineering, MIT College of Engineering, Kothrud, Pune, India Author
  • R. J. Yadav Department of Mechanical Engineering, MIT College of Engineering, Kothrud, Pune, India Author
  • P. M. Patane Department of Mechanical Engineering, MIT College of Engineering, Kothrud, Pune, India Author
  • S. R. Kale Department of Mechanical Engineering, MIT College of Engineering, Kothrud, Pune, India Author
  • Mandar M. Lele Department of Mechanical Engineering, MIT College of Engineering, Kothrud, Pune, India Author

Keywords:

Evaporative cooling, Liquid desiccants, Dehumidification cooling

Abstract

The extensive effort has made to fabricate and analyze the evaporative cooler with liquid-desiccant regeneration process. A temperature drop of around 4 degrees and a humidity reduction of around 14-16 percent as compared to direct contact evaporative cooler achieved. The enhanced average cooling efficiency of the evaporative cooler is41.828 % achieved with Average dehumidification capacity obtained at different concentrations of desiccantare: At 20% concentration of desiccant = 4.3695 lph, At 30% concentration of desiccant = 5.4845 lph, At 40% concentration of desiccant = 6.391 lph

References

Downloads

Published

2017-03-16

Issue

Section

Articles

How to Cite

Fabrication and Performance testing of Evaporative Air Cooler with Solar Liquid Desiccant Dehumidification. (2017). International Journal of Current Engineering and Technology, 1(7.Special Issue), 347-351. https://ijcet.evegenis.org/index.php/ijcet/article/view/4483